Pressure reducing & pressure sustaining valve with metal pilot

Description

The valve maintains a constant preset downstream pressure, without being affected from upstream flow and pressure variations. At the same time the valve sustains the upstream pressure at a preset minimum rate. To operate the valve uses two three way metal pilots.

If the upstream pressure remains below of the sustaining preset pressure, the valve closes completely.

Applications

Upstream pressure control and downstream pressure control.
Pump system protection against excessive demand.

Available Models

DN80 (3”), DN100 (4”), DN125 (5”), DN150 (6”), DN200 (8”), DN250 (10”), DN300 (12”)

Dimensions / Head loss

Download technical PDF

Download PDF characteristics and dimensions

Download PDF scheme

Description

References and dimensions
Product codeValveLHWKg.
DN80    892335+4963013″27526517216,0
DN100  892345 +4963014″31529020423,0
DN125  892355+4963015″31530520429,4
DN150  892365+4963016″40035030251,4
DN200  892385+4963018″56040030264,4
DN250  892410+49630110″460515372111,4
DN300  892412+49630112″580550372161,4

(Codes of valves with high pressure diaphragm AP, for valves with low pressure diaphragm BP, please consult)

Minimum working pressure
ValveLow PressureHigh Pressure
DN800,40,7
DN1000,50,7
DN1250,50,7
DN1500,61
DN2000,60,9
DN2500,71,0
DN3000,71,0